Line input |
ECTA 133, 3-Pin-Connector |
| Line input 400 V DC: |
ECTA 133, 5-Pin-Connector |
| DC-output: | High current studs (M8) |
| Alarms: | SJT00RT, 6-Pin-Connector |
| Ground terminal: | Studs M8 on front or rear |
| Protection: | IP 54 (EN 60529) |
| Cooling: | Convection cooling temperature controlled fan above +50 °C heatsink temperature |
| Operating temp. range: |
-40 °C to +70 °C |
| Derate power: | 2 % / °C for Tamb > 50 °C |
| Humidity: | 0 % to 100 % rel. |
| Salt fog: | 5 % at 35 °C |
| Vibration.: | Fig. 514.5C3 for wheeled vehicles |
| Shock: | 10 x 10 g / 6 ms |
Technical specifications
refer to data sheet: 00441
| Nominal voltage: | 400 V AC ±10 % (3 phase) and 230 V AC ±15 % (1 phase) |
| Line frequency: | 50 Hz - 60 Hz |
| Consumption: | <13 A at 230 V AC |
| Inrush current: | < 30 A |
| Harmonics (current): |
Power factor corrected to EN 61000-3-2 for 230 Vac |
| Power factor: |
typ. 0.95 (1 phase with PFC) typ. 0.80 (3 phase) |
| Output voltage: | 28 V DC (int. adj. 24 V DC - 28 V DC) |
| Output tolerance: | +0 % / -4 % / (0 % - 100 % load) |
| Output current: | 80 A at 24 V DC |
| Output power: | > 1900 W max. |
| Output voltage: | 28 V DC (int. adj. 24 V DC - 28 V DC) |
| Output tolerance: | +0 -4 % / (0 - 100 % load) |
| Output current: | 120 A for 24 V DC |
| Output power: | 2880 W max. |
| Safety: | EN 60950-1 |
| Output protection: | Current limit (120 % of INom) Short circuit protection Over voltage shutdown (125 %) Over temperature shutdown with automatic recovery |
| Minimum load: | no minimum load required |
| Efficiency: | typ. 88 % at 400 V AC typ. 83 % at 230 V AC |
| Isolation: | Input-Output: 3000 V AC Input-Chassis: 1500 V AC Output-Chassis: 200 V DC |
| Display: | Green LED: Power-on-signal Red LED: Alarm (batt-low) |
| Alarms (Relay contact): |
Power ok, Battery-low |
| Dimensions:: | 360 x 500 x 124 mm (W x D x H) (overall, without connectors) |
| Weight: | approx. 16 kg |
| Material: | Aluminium |
| Finish / Colour: | Powder coating, green RAL 6031 or TBD |
| Line Input Voltages: | Single Phase 110 V AC 60 Hz or 95 V AC - 264 V AC, 50 Hz / 60 Hz (Wide Range Input) |
| Line filter / EMC: | FCC / EN / VG / MILStandards / TBD |
| RoHS-compliance: | On request |