Technical specifications
refer to data sheet: 01279
Continuous output power: | 1000 VA |
Maximum output power (1 min.): | 1150 VA |
Surge rating (1 sec.): | 1750 VA |
Input voltage (nominal): | 24 V DC |
Input voltage: | 21 V DC to 33 V DC |
Output voltage: | 230 V AC +/- 5 % |
Output frequency: | 50 Hz +/- 0.5 % |
Output waveform: | Pure sine wave (THD < 5 %) |
Efficiency (full load): | 89 % |
No load current: | < 0.8 A |
Standby current: | < 0.05 A |
Input level indicator: | Red / orange / green LED |
Load level indicator: | Red / orange / green LED |
Failure indicator: | Red LED |
Protection: | Overload, short circuit, over- / under- input voltage, over temperature, residual-current device (RCD) +40 °C to +60 °C derating 400 VA max. |
Safety: | EN60950 |
EMC: | EN55022, EN55024, EN61000-4-2, 3, 4, 5, 6, 8, 11 EN6100-3-2, -3-3, MIL-STD461G, CE102 (Basic Curve), RE102-4 (Navy Fixed & Air Force) |
Electrical isolation input / output: | Isolation test voltage 500 V DC |
Temperature: | -31 °C to +40 °C (operating) -40 °C to +70 °C (storage) |
Cooling: | Convection |
Dimensions: | 420 x 180 x 86 mm (W x D x H) |
Weight: | approx. 7.5 kg |
Protection: | IP 65 |