This power supply / battery charger based on a new concept with a high frequency transformer which also provides the high isolation (reinforced) between input and output.
The new technology allows a weight reduction of up to 70 % (compared with existing 50 Hz / 60 Hz transformers).
The internal high frequency transformer generates also an additional 230 V AC output at about 1 kVA. Output power can be shared between the 24 V DC and 230 V AC output. RCD-Protection is optional available.
Optical indicator: | Green LED: Power ok Red LED: Battery low White LED: 230 V AC-Out active |
Material: | Aluminium |
Dimensions: | 360 x 500 x 145 mm (W x D x H) (overall dimensions) |
Weight: | < 20 kg |
Finish / Colour: | Powder coating, green RAL 6031 Hr or TBD |
Line input: | ECTA 133, 3 Pin Connector |
Output: | CEE-Connector (3 pin) or VG96926 |
Alarm: | SJT00RT, 6 Pin Connector |
Output DC: | High current studs M8 isolated |
Grounding terminal: | M8 on front or rear |
Technical specifications
refer to data sheet: 00950
Nominal voltage: | 230 V AC ±15 % |
Line frequency: | 45 Hz to 60 Hz |
Consumption: | < 16 A |
Inrush current: | < 30 A |
Harmonics (current): |
Power factor corrected to EN 61000-3-2 |
Power factor: |
> 0.95 |
Output voltage: | 24 V DC (adj. 24-28 V DC) |
Output tolerance: | -4 % / +0 % (0 –100 % load) |
Output current: | 80 / 100 A (depending on model) |
Output protection: | Current limit (110 % of INom) Short circuit protection Over voltage shutdown (125 %) Over temperature shutdown with automatic recovery |
Minimum load: | no minimum load required |
Efficiency: | typ. 85 % – 88 % at 230 V AC |
Output voltage: | 230 V AC 50 Hz 110 V AC optional |
Output tolerance: | ± 8 % |
Output current: | 4 A - 6 A |
Output protection: | Short circuit protection Over voltage shutdown Over temperature shutdown with automatic recovery |
Minimum load: | no minimum load required |
Efficiency: | typ. 89 % at 230 V AC |
Isolation voltage: | 4000 Vac (input – output) 3000 Vac (chassis – line) |
Protection class: | II no PE |
Temperature: | -20 °C to +50 °C (operating) -40 °C to +85 °C (storage) |
Vibration / Shock: | TBD |
Protection: | IP 65 (EN 60529) |
Line Filter / EMC: | FCC / EN / VG / MIL Standards / TBD |
Input voltage: | 400 V AC 50 Hz |